							PMT25100 Series Precision Fixed-Ratio Current Transformers
							
						 
							Precision two-stage toroidal current transformers find application as the reference in
							determining the accuracy of instrumentation current	transformers.
 The better than 50ppm (0.005%) accuracy in passive operation at 0.5VA common burden
							(typical Comparator burden) is further improved by activating an electronic processing
							circuit that effectively removes core flux caused by voltage induced secondary burden.
							Battery powered electronic burden cancellation improves the accuracy by typically a factor
							of five approaching 10ppm (0.001%).
 
 The primary current conductor, typically a bus-bar or flexible cable, is threaded through
							the centre hole with one or more turns.
 
 Several models feature wound primary turns to facilitate operation at lower current operation.
 
 Models are available with or without electronic burden cancellation as well as a 5 ampere or 1 ampere
							normalized secondary current.
 
 
 
							--- Current Transformer Features ---
							
						 
							High Accuracy and Linearity
 
 Toroidal Two-Stage, Zero Flux Design
 
 Passive and Active (Electronic) Operation
 
 Primary Currents from 5 to 500 Amperes
 
 5 Amp or 1 Amp Secondary
 
 Open-Circuit Secondary Protection
 
 Models from 100:5 to 6000:5 are available
 
 |